• ADM loop technology with
System Sensor/200 protocol
• Two input lines monitored for wire
breakage and short circuit
• One dry relay output
• Setting of module address via
decadic rotary switches
• Mounting in module box or by means
of mounting base
Description
The addressable Module M221E serves for the line-
monitored integration of 2 contact detectors, such as
manual call points, sprinkler system contacts or super-
vising contacts, into the bidirectional communication
on the ADM loop with System Sensor/200 protocol.
Furthermore, it can be used to actuate external de-
vices by means of a relay output with a dry change-
over contact, via the ADM loop. Each input as well as
the output have individual status LEDs. Separate termi-
nals enable the operation of the module with or without
the integrated dual-isolator.
Accessories for mounting on a wall, on a plate or on a
DIN rail are available.
Specifications
Operating voltage
Current consumption
Contact rating
Ambient temperature
Dimensions L × W × H
Colour
Supply through loop voltage
approx. 660µA (quiescent)
2A/30VDC or 0.5A/125VAC
-20°C to +60°C
93 × 94 × 23 (mm)
cream
Weight
110g
Approval
VdS G202139
Order number
Order name
249102
Module 2xSurv.In 1xRel.Out/Anal./200/SS M221E
Building Safety. Building Security.
A
© LABOR STRAUSS SICHERUNGSANLAGENBAU GMBH • A-1231 WIEN • WIEGELESTRASSE 36 • TEL +43 1 52114-0 • FAX +43 1 52114-27
M221E_DBL_LST_EN_0804.PDF • PAGE 1
OFFICE@LST.AT • WWW.LST.AT • ALL RIGHTS RESERVED
|
KTI Networks Switch KSD 800 User Manual
Land Pride Brush Cutter RC25 User Manual
Learning Resources Watch LER 2288 User Manual
Lenovo Laptop E49 User Manual
LG Electronics Cell Phone Chocolate Blue Ice User Manual
Liebherr Beverage Dispenser WS 40 User Manual
Life Fitness Home Gym SM42 User Manual
Lincoln Automobile 2006 LS User Manual
Maytag Clothes Dryer MED9700SB0 User Manual
Melissa Styling Iron 635 086 User Manual